PF2100
Modbus Card Instruction Manual v1.1
©2011 Profire Energy Inc
Jan 5, 2012
Page 22
The “TX” LED Does Not Light When the Master Sends a Command
The address is incorrect, the wiring is incorrect, the baud rate is incorrect, or the card is damaged.
Double check that the Modbus Card has the correct address in the menu 6.8.
Double check that the Master is using the correct address to talk to the Modbus Card
Double check the wiring of the card and the master device
Double check the baud rate settings for the card and the master device
Contact Profire to arrange for a hardware repair or replacement.
The “TX” LED Blinks but the Master Receives Garbage Data
The Modbus Card may be responding before the Master is ready. This problem may be common when certain types of repeaters are used on the bus.
Try changing the Rx to Tx delay from 2ms to 25ms using the DIP switch.